PRODUCTS & SERVICE
AMR/AMI Energy Meter
Single-phase AMR/AMI Energy Meter
Single Phase AMI Smart Energy Meter

DDSD285 single phase AMMmeter with advanced security features, modular communication and optional  isconnect functionality, ready for smart Grid. Easy installation and system set-up, reliable operation and various communication (PLC/GPRS/Zigbee) choice and carefree maintenance create the perfect solution for AMM system.


Item 

Parameter 

Accuracy (kWh) 

Class B (EN 50470-3)  or  Class 1 (IEC 62053-21) 

Accuracy  (kvarh) 

Class 2 (IEC 62053-23) 

Basic current Ib 

10A 

Maximum current Imax 

100A(Direct connection) 

Minimum current 

0.05Ib 

Starting current 

0.004Ib(Direct connection) 

Rated voltage Un 

230 V 

Operating voltage range  

85~480V (Wide voltage range) 

Operating frequency 

50Hz 

Communication interface 

1 circuit optical interface; 
1 circuit Connect to external GPRS module; 
1circuit M-bus wired module built-in (optional) ; 
1circuit RJ11 wired module built-in(optional) ;

Communication Protocol

Optical: IEC62056-21 E mode
GPRS: DLMS/COSEM
M-Bus: En13757-3
RJ11: IEC62056-21 D mode

optical interface 

IEC/EN standards 

Relay 

1 Main contactor (100A);  

RTC 

≤0.5s/day(Normal temperature) 

RTC support 

10 years battery operation life 
Operating for at least 2 years in case of any power failure 

Backup battery 

Battery can be replaced 
Ultra capacitor can maintain RTC for at least 5 minutes 

Pulse constant 

1000 

Power consumption 

Current circuit power sumption≦1VA 
Voltage circuit power sumption≦2W/10VA 

Compression strength 

4kV, 50Hz, 1 minute 

Anti-surge 
Voltage 
Current 

6kV, 1.2/50μs 
5kA, 8/20μs 

Immunity to short-circuit current 

30Imax 

Immunity to electrical fast 
Transients/bursts (EFTB) 

4 kV (IEC 61000-4-4) 

Anti-magnetic 

anti-strong magnetic, magnetic detection and display 

Operating temperature range 

-25°C ~ +70°C 

Storage temperature 

-40°C ~ +85°C 


1. Measurement

Import/Export active energy 
Instantaneous value measurement
--(current/voltage/Active power/Power Factor/Apparent power of each phase)

 

2. Tampering&Event

Meter Cover open detection and record
Meter terminal open detection and record
Current reverse detection
Large magnetic effects
Over voltage/Overload

 

3. Load profile&Max Demand&Billing

Support load profile, interval can be setting.
kWh maximum demand and time stamp;
12-Month Billing Data(optional)

4. Communication 

Local: Optical interface/1 RS485;
Remote: GPRS/PLC/RF wireless communication.
Protocol compatible to (Local)IEC62056-21 and (Remote)DLMS HDLC or IEC62056-21;

 

5. AMI Function

Meter Data Management System;
Real-time event monitor;
On-time Data Report;
Remote relay control.